TABLE III

RECOMMENDED INSTRUMENT-TRANSFORMER CABINET SIZES

Conductors  Number of

Installation
Type
Installation
Voltage
Max # per
Phase
Service
Size (KCM)
Transformer
Cabinet Size
Inches
Hinged Doors
Required
1-Phase 120/240

1
2
2
3

750 or Less
500 or Less
600 to 750
500 or Less

24 x 24 x 10
24 x 32 x 10
24 x 42 x 12*
24 x 42 x 12*

1
1
2
2

3-Phase
3-Wire

230

1
2
2
3
3
4

750 or Less
500 or Less
600 to 750
500 or Less
600 to 750
750 or Less

24 x 32 x 10
24 x 32 x 10
24 x 42 x 12*
24 x 42 x 12*
38 x 60 x 18***
38 x 60 x 18

1
1
2
2
2
2

3-Phase
4-Wire

120/208

1
1
2
3
3
4

500 or Less
600 to 750
750 or Less
500 or Less
600 to 750
750 or Less

24 x 32 x 10
24 x 42 x 12*
24 x 42 x 12*
24 x 42 x 12*
38 x 60 x 18***
38 x 60 x 18

1
1
2
2
2
2

3-Phase
3-Wire

460

1
1
2
3
4

350 or Less
400 to 750
750 or Less
750 or Less
750 or Less

24 x 32 x 10
24 x 42 x 12*
24 x 42 x 12*
38 x 60 x 18***
38 x 60 x 18

1
2
2
2
2

3-Phase
4-Wire

277/480

1
2
2
3
4

750 or Less
500 or Less
600 to 750
750 or Less
750 or Less

24 x 42 x 12*
24 x 42 x 12*
38 x 60 x 18
38 x 60 x 18
38 x 60 x 18

2
2
2
2
2

3-Phase
3-Wire or
4-Wire

2400 or
2400/4160

1
1

500 or Less
500 or Less

36 x 60 x 36
36 x 60 x 36

2**
2**

The sizes listed are minimums. There may be cases where a larger cabinet is necessary based on factors listed in Section 8.7.1.
*If a 24 x 42 x 12 cabinet is not available, one 36 x 36 x 10 may be substituted.
**For floor or ground level cabinets, 1 hinged door is preferred.
*** If a 38 x 42 x 12 cabinet is not available, a 48 x 48 x 18 may be substituted.
Instrument cabinets shall be furnished and installed by the Customer.