TABLE I
SINGLE-PHASE METERING EQUIPMENT
Meter Socket
Maximum
Service Conductor
Approximate Socket Size in Inches
Type Of
Code
Amperes
Size
D
W
L
Service
Application
S-100
100
Maximum Size #1 AWG
3-1/2
8-1/2
10
Overhead Only
100 Amperes or Less and services requiring current transformers
U-150
150
1/0-2/0
4-1/2
14
Underground Only
150 Amperes or less
S-200
200
1/0 250 KCM
150 & 200 Ampheres Residential
U-200
200 Amperes Residential
H-200
19
Overhead Or Underground
200 Ampere commercial & industrial with demands under 35 kVA
400 Ampere Transocket
400
250-750 KCM
11
24
30
200 to 400 Ampere with demands over 35 kVA
GV2
GV & GH Line
4
8-1/4
20
Vertical 2 position gang socket for two individual 150 ampere services
GH-2 GH-2-2
150 200
Side 1/0 To 250 KCM Load
4-3/4 5
20-1/2 28
12 16
Horizontal gang meter sockets for 2 to 6 positions
GH-3 GH-3-2
Side Maximum 2/0 Al or
32-1/2 36
GH For individual services rated 150 amperes or less. Total service requirements
GH-4 GH-4-2
1/0 Cu GH - # - 2 Line
41 45
Shall Not Exceed! 300 Amperes for Cu or 225 Amperes for Al
GH-5 GH-5-2
Side 1/0 To 600 KCM Load
49 55
GH - # - 2 For individual services rated 200 amperes or less. Total service requirements
GH-6 GH-6-2
Side Maximum 250 KCM
57-1/2 62
Shall Not Exceed! 400 Amperes for Cu or 400 Amperes for Al
Instrument-Cabinet Installations
200 And Up
One or More Per Phase
8 x 14 inch Single Meter Socket Overhead or Underground See Table III
Where The Service Size Exceeds Those Described Above