Instrument
Transformers In Cabinets
Instrument transformers
shall not be mounted
directly on the back
surface of instrument
transformer cabinets, but
shall be mounted on a 3/4
inch plywood panel or on
mounting plates or
brackets. The polarity
marks (red dot) shall face
the line side. Instrument
transformers shall be
mounted so that they may
be readily removed or
replaced. Where bar-type
current transformers are
used, the connections
shall be on the back side
of the primary bar of the
current transformers, with
the nuts of the bolts on
the front side. Where
through-type current
transformers are used, the
conductors shall be broken
on the line side of the
current transformer and
reconnected with adequate
bolted connectors. See
Figure 18.
Instrument
Transformers In Switchgear
When instrument
transformers are installed
in Customer's metal-clad
switchgear, the Customer
shall arrange to have the
supplier furnish detailed
drawings of the switchgear
and instrument transformer
arrangement. These
drawings shall be
forwarded to the Energy
Technology Services
Department for acceptance
and approval before
constructing the
switchgear. The Energy
Technology Services
Department on request will
supply information on the
size, type and number of
instrument transformers to
be furnished.
The instrument transformer
compartment shall be
completely separated by a
rigid barrier from the
rest of the switchgear. It
shall have hinged doors
which are sealable with
pad lock type sealing
devices. It shall be large
enough to contain the
required number of
through-type current
transformers and voltage
transformers for services
of 277/480V and higher.
The design shall be such
that the transformers can
be readily installed or
changed after the
switchgear is in place.
Removable sections of bus
bar shall be provided as
the primary conductor of
the current transformers,
and shall be the same
ampacity as the bus bar
entering and exiting the
compartment. It may also
be necessary to parallel
narrower bars to
accommodate the CTs
supplied by the Company.
The instrument
transformers shall be
installed by the Customer.
They shall be located on
the line side of the main
switch or circuit breaker.
The service-entrance
conductors shall be
completely enclosed in
conduit or raceway from
the service point to where
they enter the switchgear
instrument transformer
compartment. All service
and metering conductors
exiting the instrument
transformer compartment
shall not be returned to
the compartment. Voltage
connections for metering
shall be provided in the
compartment. These
connections shall be on
each phase bus on the line
side of the current
transformers, and for
three-phase, four-wire
services shall also be on
the neutral. In
installations where the
service is four-wire but
the load is three-wire, a
neutral conductor shall be
extended to the CT
compartment.
|
|