|
Meter
Socket Grounding
Meter sockets or
enclosures shall not be
used for the purpose of
grounding cable TV,
telephone, or any other
service lines.
Self contained meter
sockets and transockets
shall not be separately
grounded unless the
electrical inspection
agency requires the
neutral conductor to be
isolated in the socket, or
the socket is used on an
ungrounded 230 volt
service.
All instrument transformer
rated sockets and
enclosures shall be
grounded. Refer to Figure
23.
Refer to Section
3.4 Service Grounding
for more information.
MULTIMETER
INSTALLATIONS
Meters for all Customers
in a multiple-occupancy
building shall be grouped
in a minimum of locations.
For all multimeter
installations, the
Customer, electrical
contractor, or builder
shall submit a detailed
plan to the Energy
Technology Services
Department for its
approval before equipment
is purchased or meter
installation is started.
The meter socket and main
service equipment for each
individual apartment,
office, or storeroom shall
be clearly and permanently
identified by the Customer
or his electrical
contractor. If changes in
apartment numbers are made
after the meters are set,
the Company shall be
notified immediately by
calling Customer Relations
at 412-393-7100.
For installations of two
to six meters, the
service-entrance
conductors shall enter the
top or bottom of the meter
socket, as shown in Figure 19.
When entering the top, a
hub shall be used. Hub
openings not used shall be
covered with a closure
plate.
For multimeter
installations of more than
six meters, a circuit
breaker or a switch with
fuses shall be installed
on the supply side of the
meters. The unmetered
conductors shall be
brought out of the switch
or breaker compartment in
metallic conduit to a
sealable wireway or wiring
trough. All taps to the
meter socket shall be made
in the wireway or wiring
trough as shown in Figure 20.
If the building owner
elects to use prewired,
combination multiple meter
and breaker panels for
multimeter installations,
the complete panels shall
be furnished by the owner.
A list of approved
manufacturers of prewired,
combination multiple meter
and breaker panels is
available from the Energy
Technology Services
Department. Prior to
purchasing, the details of
all equipment and the
installation plan shall be
submitted to the Energy
Technology Services
Department for approval.
The essential requirements
for this equipment are the
use of Belleville-type
washers and oxide
inhibitor on all aluminum
to aluminum connections,
provision for installation
of a fifth terminal in the
9 o'clock position of each
120/240 volt, single-phase
meter socket, sealable
separate compartments for
unmetered wiring, and no
metered and unmetered
wiring in the same
compartment. A typical
installation of prewired
equipment is shown in Figure 21.
In multimeter
installations where meter
sockets are located on the
load side of the service
disconnecting means, and
where the neutral is
grounded to the case of
the service disconnecting
means, local electrical
inspectors may require
that the neutral bus in
the meter sockets be
isolated from the meter
socket frame. However,
such isolation of the
neutral conductors in the
meter socket is not
usually required if the
meter socket is located
within view in the same
room near the service
disconnecting means.
|
|