MAINTENANCE OF SERVICE EQUIPMENT It is the Customer's responsibility to maintain all structures, equipment and associated devices owned by him so as to ensure their proper operation at all times. The Company may require the Customer to demonstrate that the service equipment has been maintained and will operate properly. The demonstration may include a station battery and battery charger inspection, fuse inspection, circuit breaker trip checks, circuit verification checks, relay operating checks, etc. The Customer shall be responsible for damage to Company equipment caused by the failure of service equipment to operate properly. MOBILE SUBSTATION CONNECTION REQUIREMENTS When a service installation is being planned, the Company may anticipate the use of a mobile substation as a future temporary source of supply during the course of maintenance, inspection or tests by the Company. Upon request by the Company, the Customer shall provide parking space of approximately l5 by 25 feet for the mobile substation. The location of the parking space shall be such that 50 foot conductors can be used to connect the mobile substation to the service line and to the load side of the service equipment. The parking space shall not block access for removal or replacement of transformers and equipment using Company cranes and trailers. The Customer shall provide suitable connectors for a single connection point per phase on the load side of the service equipment to permit connection of the mobile substation. The Customer shall also provide openings in both the Company and Customer portions of the substation or vault to accommodate the high and low voltage conductors from the mobile unit.
|
|||
|
|
|
||
|
|||