REWIRES, CHANGES AND ADDITIONS All existing electrical services have a maximum design capacity. The Customer shall provide the Division Office with information on any proposed changes or additions before new equipment is ordered. The Company will determine if changes to its supply facilities are necessary and whether the service and equipment are compatible. Changes or additions to Customer's wiring or equipment are subject to the same Company rules as new services. Wiring and service equipment that has been changed will not be energized by the Company until such wiring and service equipment is inspected and approved as specified in Section 3.3. For any service wiring changes for which the Company has not specified a new meter location, the Customer shall comply with the following general guidelines: (a) Residential meters located indoors shall be moved to outdoor locations as specified below and in Section 4.2.3(d). (b) Meters other than residential may be required to be moved outdoors. (c) New meter locations shall be chosen to eliminate house to house connections and service drops over roofs, awnings and other structures. (d) Meters shall be readily accessible to Company representatives. The best location is on the side of the building at the front corner nearest to the Company's service pole or underground service point. Contact the Division Office if there are problems applying these guidelines.
|
|||
|
|
|
||
|
|||