Duquesne Light  

TYPES OF ELECTRIC SERVICE, DISTRIBUTION

SERVICES AND DEMAND LIMITS AVAILABLE FROM DISTRIBUTION SUPPLY LINES, OPERATING AT 2,400 VOLTS OR HIGHER WITH FACILITIES LOCATED ON CUSTOMER’S PROPERTY

SUPPLY LINE VOLTAGE
THREE-PHASE, FOUR-WIRE CIRCUITS

TYPE OF SERVICE

2,400/4,160 VOLTS

13,200/23,000 VOLTS

VOLTAGE

PHASE

WIRES

OVERHEAD
LIMITS (kVA)
Min.-Max.

UNDERGROUND
LIMITS (kVA)
Min-Max.

OVERHEAD
LIMITS (kVA)
Min.-Max)

UNDERGROUND
LIMITS (kVA)
Min-Max.

120/240

1

3

1-50

1-50

1-100

1-100

230/460

1

3

1-50

NOT AVAILABLE

1-100

NOT AVAILABLE

120/208

3

4

30-300

50-500

30-300

50-1,500

230

1

2

1-50

1-50

1-100

1-100

230

3

3

1-300

50-500

1-300

50-1,000

277/480

3

4

NOT AVAILABLE

150-500

50-500

150-2,000

460

1

2

1-50

NOT AVAILABLE

1-100

NOT AVAILABLE

460

3

3

50-500

150-500

50-500

150-2,000

2,400

1

2

1-50

NOT AVAILABLE

50-100

NOT AVAILABLE

2,400

3

3

NOT AVAILABLE

NOT AVAILABLE

NOT AVAILABLE

225-2,000

2,400/4,160

3

4

150-500

150-500

150-500

225-2,000

13,200/23,000

3

4

NOT AVAILABLE

NOT AVAILABLE

500-2,000

500-2,000

NOTE: HIGHER LIMITS ARE AVAILABLE IN SOME LOCATIONS. CHECK WITH THE COMPANY



Terms of Use | Site Map | Site Help | © Copyright 2007