Duquesne Light  

TYPES OF ELECTRIC SERVICE, SECONDARY

SERVICES AND DEMAND LIMITS AVAILABLE FROM STREET SECONDARY SUPPLY LINES, OPERATING AT LESS THAN 300 VOLTS

TYPE OF SERVICE

APPLICATION LIMITS

LOAD LIMITS

TYPE

VOLTAGE

PHASE

WIRES

 

OVERHEAD
LIMITS (kVA)
MAXMUM.

UNDERGROUND
LIMITS (kVA)
MAXMUM

A

120

1

2

SPECIAL APPLICATIONS ONLY

2.4

2.4

B

120/240

1

3

LIGHTING, APPLIANCES, RESISTANCE
HEATING AND MOTORS

50

25

C

120/208

1

3

LIGHTING, APPLIANCES, RESISTANCE
HEATING AND MOTORS

25

25

D

120/208

3

4

LIGHTING AND POWER

50

150

E

230

1

2

SPECIAL POWER USES ONLY

50

NOT AVAILABLE

F

230

3

3

POWER WITHOUT LIGHTING

112.5

75

SERVICE TYPES B & C ARE NOT AVAILABLE AT THE SAME LOCATIONS.

SERVICE TYPES D & F ARE NOT AVAILABLE AT THE SAME LOCATIONS.

SERVICE TYPE D SUPPLIES BOTH LIGHTING AND POWER LOADS AT LOCATIONS WHERE IT IS AVAILABLE.

SERVICE TYPES B & F SUPPLY LIGHTING AND POWER LOADS AT LOCATIONS WHERE THESE SERVICES ARE AVAILABLE.

HIGHER LIMITS ARE AVAILABLE AT SOME LOCATIONS. CHECK WITH THE COMPANY.